Permit Number | FIR10-00117 |
Status | Finaled |
Name |
ABSOLUTE FIRE PROTECTION
|
Site Address |
1399 S EAGLE FLIGHT WAY
|
Project Name | Alaskan Airlines |
Customer Number | |
ePlanReview | |
Description |
The Fire Sprinkler Scope of work consists of adding and relocating sprinklers to accommodate a new tenant improvement. The existing system is a 2½"x2"'x1¼" grid. The original calculations were reported as .10/1546 with a minimum flow of 22.5 gpm @ 16.14 psi total demand of 253.68 gpm @ 44.84 psi with a cushion of 8.74 psi. Original permits were reported as FIR00-00628 and FIR01-00022 All sprinklers are indicated as quick response type.
(ALASKAN AIRLINES - Call Center) Permit is to remodel an existing 14,412 square tenant space, this space will be downgraded to 9,689 square feet and is located on the South side of the building. Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create a separation from the remainder of the building, create a communications room, a communications support room, and a conference room], minor electrical modifications, minor mechanical modifications, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
|