Description |
This quick permit is to provide a new strobe for a new copy room created by the tenant improvement. The device will be added to the existing system. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. There are no written comments. Associated building permit: BLD10-00087 (Casey Family Programs) Permit for minor tenant improvements to an existing 9,939 sq. ft. tenant space with work to include the removal of a a small section of pony wall and misc. millwork, misc. lighting and the construction of approximately 28 lineal feet of interior partition wall to create a new copier room. All work to be done per the approved plans. CDM
|