Permit Information
Permit NumberFIR10-00203
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 5373 W EMERALD ST
Project NameCapitol Auto Body - Addition
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of fire protection for a new addition. The new addition contains a spray booth. The area above and surrounding the booth will be protected as ordinary hazard group II. The spray booth will be protected as Extra Hazard II. A loop will be provided to control the spray booth. The new addition will be connected to the existing riser.

Plan Mod 1 Scope:
The spray booth was changed to a downdraft. Therefore, the fire protection design required alterations. An exception was given to protect just protect below the filter and not above. This was due to impractically reasons since the underground is existing. The sprinklers will be no more than 12” below the deck. Therefore, it is anticipated that the sprinkler actuation time will not be impaired. This exception was approved by the fire code official. The prep area was also redesigned due to field conditions. Ballooned areas reviewed

Plan Mod 2 Scope:
Revised pipe sizes and minor layout changes.

Capitol Auto Body - Shop Addition - To construct a 933 square foot addition to the South side of an existing 6,072 square foot Auto Body Shop, remove an existing 24' X 26' wood framed garage structure, and renovate an existing outdoor open air storage area "pole barn structure". Work to include: Construct the new shop addition with 8-inch block/concrete masonry unit walls with metal cap and flashing; including installing a 10/0 X 10/0 retractable garage door, a 9/0 X 9/0 double metal swing door, a 3/6 X 7/0 metal equipment storage door; install a membrane roof on a wood truss system; and install a wood truss canopy system to the front exterior wall. Enclose the existing open storage area with 8-inch block/concrete masonry unit walls on three sides; partially remove and modify the existing mono roof truss, column and beam systems; provide new concrete bearing for some of the existing 8 X 8 wood bearing columns; repair/patch some existing asphalt paving and install a "Nova Verta" pre-manufactured paint booth. All work per the approved plans, Engineering, attached plan review report, and all other reviewing agencies approvals. The existing paint/preparation area is partially fire sprinklered. Any modifications or alterations to the existing sprinkler system WILL require a separate permit. DRH09-00272 and CUP09-00084 per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/23/201012/23/201012/23/2010PPASS
DetailsTroy Cobbley
Permit finaleed. A fire alarm system is not required per scott arellano.
INSP-Sprinkler Rough-in/Hydro12/22/201012/22/201012/22/2010PPART
DetailsTroy Cobbley
The hydro test passed but I was unable to perform a rough-in inspection due to the latest approved plans were still being reviewed.
FIR-Aging Inspection11/30/201011/30/201012/2/2010 NR
DetailsTroy Cobbley
work is in progress
FIR-Aging Inspection9/15/20109/15/20109/21/2010 NR
DetailsTroy Cobbley
Per Granite Cont. all work should be complete within a couple of weeks.