Permit Information
Permit NumberFIR10-00258
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1819 W BANNOCK ST
Project NameAmber Lane Assisted Living
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of a modified 13D sprinkler system. Sprinklers are required in all rooms. The system is supplied by a 2" polypipe, 1¼" riser with a 1¼" backflow preventer. The system has a 1¼" main and 1" branch lines.

There is no associated building permit
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/26/20108/27/20108/27/2010PPASS
DetailsForrest France
Fire sprinkler permit final approved.
INSP-Final Inspection8/10/20108/10/20108/10/2010PPART
DetailsForrest France
Final pending riser supervision.
INSP-Final Inspection8/6/20108/9/20108/9/2010PPART
DetailsForrest France
Correction items verified for completion. Final pending project related fire alarm permit work.
INSP-Sprinkler Rough-in/Hydro7/29/20107/29/20107/29/2010APART
DetailsForrest France
Ref. stamped plans on site for inspection notes at the overhead install.
INSP-Supply line flush7/16/20107/19/20107/19/2010APASS
DetailsTroy Cobbley
The underground flush passed.
INSP-Sprinkler Rough-in7/13/20107/14/20107/15/2010APART
DetailsForrest France
UG fire supply line approved for bury.
INSP-Conference7/13/20107/13/20107/13/2010PDONE
DetailsForrest France
Regarding underground fire supply line installation.
INSP-Sprinkler Rough-in7/9/20107/12/20107/12/2010PFAIL
DetailsForrest France
Missing tenting at one section of piping in the attic, provide one missing hanger at an armover, noted five locations where pendent heads are obstructed per NFPA 13D 2007 sec. 8.2.5.2.1.