Permit Number | FIR10-00467 |
Status | Finaled |
Name |
R M E INC
|
Site Address |
805 W IDAHO ST
|
Project Name | 3RD FLOOR VANILLA T.I. |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide notification in the common and public spaces in this third floor tenant area. There are no initiating devices in this scope of work. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V - 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. A building map shall be posted at the FACP indicating the type and location of all alarm initiating devices, by device address or zone number. Provide updated map reflecting the floor plan and all initiating device locations. 2007 NFPA 72 4.4.6.1.There is no associated building permit.
|