Permit Information
Permit NumberFIR10-00515
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 11311 W CHINDEN BLVD
Project NameHEWLETT PACKARD
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of providing extended coverage sprinklers to protect a new storage area in an existing building. The storage is group A plastic on single row racks. Storage height is 13’-5” with < 5’ clearance to the deck. There will be no solid shelved or plastic pallets and no idle pallet storage. The existing fire protection is being removed and capped. The work will begin at an existing 8” riser new 6” main will supply 3” branch lines. Per the designer, the space is compartmentized therefore; the protection was not needed to extend 15’ into the other spaces.


Building Department Scope:

(FACILITIES PERMIT) (HEWLETT PACKARD - BLD 1 FLR 1 - RACKING) This project is for the installation of 104 LN/FT of 12ft high racking. per engineering
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/25/201010/25/201010/26/2010PPASS
DetailsForrest France
Hydrostatic test completed acceptable. Final inspection passed, permit finaled.
INSP-Sprinkler Rough-in/Hydro10/25/201010/25/201010/25/2010APASS
DetailsTroy Cobbley
Rough-in passed. Permit can be finaled when the hydro test passes. Could not begin the hydro test due to the protection for the Remstar unit had not been completed.