Permit Information
Permit NumberFIR10-00529
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 7 IDF COOLING
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide a new smoke detector w/relay base for FCU shutdown (full area detection) in the telecomm. room. The device will be added to the nearest Mapnet circuit on the existing fire alarm control panel. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20111/18/20111/19/2011PPASS
DetailsForrest France
Fire alarm permit finaled.
FIR-Aging Inspection1/3/20111/3/20111/10/2011 NR
DetailsTroy Cobbley
Per charlie this will be called in within the next couple of weeks with building 5
INSP-Final Inspection11/1/201011/2/201011/3/2010APART
DetailsForrest France
Functional testing passed. However, drop ceiling must be replaced where missing to ensure proper operation of the new smoke detector.