Permit NumberFIR10-00579
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8605 W FAIRVIEW AVE
Project NameDennis Dillion - Fairview
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of a wet pipe system for a new addition. The system is protecting Class IIIB IC flammable liquids located in the pit. Flammable liquids are NOT permitted in any other location within the building, unless a redesigned sprinkler system plan is resubmitted. The overhead system is designed the same as the pit within a 15’ direction surrounding the pit openings. The remainder of the system is design as Ordinary Hazard Group II. The dry system was permitted under FIR10-00510. The system is supplied through 6” underground to a 4” backflow preventer to a 6” riser. The branch piping sizes varies. There are a mixture of standard and quick response sprinklers. The separation is at the north south wall where the building's new wing turns east. The pit sprinklers and the sprinklers above the pit are 286º.


Building Department Scope:

Dennis Dillon Nissan - Addition and Remodel - To add onto and remodel two existing building to create a new 30,130 square foot, one story Nissan automobile dealership. The existing 10,365 square foot building, on the northwest corner will be remodeled into a showroom and sales area. The existing 4,860 square foot, premanufactured steel building on the south west corner will be converted into a parts storage and sales area. A new 11,815 pre-engineered steel building addition will be constructed on the southeast side of the building for a service area and a 3,045 square foot, wood framed addition will be constructed to tie all of the building together. This area will contain a retail area, parts and service manager’s offices, tire storage, parts storage and part of the parts tech area. This permit also includes related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/4/20114/4/20114/4/2011PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection4/1/20114/4/20114/4/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection3/24/20113/28/20113/28/2011AFAIL
DetailsTroy Cobbley
The forward flush passed. The other items from the previous correction notice needs addressed.
INSP-Final Inspection3/23/20113/24/20113/24/2011AFAIL
DetailsForrest France
Final pending forward flow test sufficient to meet system demand, reliable heating at the riser room to maintain ambient temperature above 40 deg., signage at the doors to the riser. Alarm interconnections tested okay.
FIR-Aging Inspection3/23/20113/23/20113/23/2011PCANC
DetailsTroy Cobbley
wrong inspection type set up.
INSP-Sprinkler Rough-in3/23/20113/23/20113/23/2011PPASS
DetailsTroy Cobbley
The lighting obstructions have been addressed and the extended coverage head is ok. Items needing addressed are the typical final inspection items such as tagging, signage, backflow certification and forward flow test.....ect
INSP-Sprinkler Rough-in/Hydro3/14/20113/14/20113/14/2011PPASS
DetailsTroy Cobbley
The wet system hydro test passed.
INSP-Sprinkler Rough-in3/10/20113/10/20113/10/2011PPASS
DetailsTroy Cobbley
Remaining sprinkler rough-in passed. Noted additional fittings affecting remote areas 2 and 3 but per Tim the hydraulic calculations are adequate. I also noted side wall heads under overhead doors that were not shown on the plans. One door at the east end of the service bay is going to be provided with an extended coverage sidewall that will need to be field approved. I also noted that the existing pendant sprinklers in the sales area are being blocked by suspended light fixtures. This problem will need to be addressed prior to final sign off. It appears that if the lights are mounted to the ceiling they will no longer be an obstruction.
INSP-Sprinkler Rough-in/Hydro3/9/20113/9/20113/10/2011APART
DetailsForrest France
24 hr. pneumatic testing of the dry system passed with no pressure loss at the guage.
INSP-Sprinkler Rough-in3/8/20113/8/20113/9/2011PPART
DetailsForrest France
Begin 24 hr. pneumatic test of the dry system at 10:30 AM 3/8 @ 42psig.
INSP-Sprinkler Rough-in1/21/20111/21/20111/21/2011PPASS
DetailsTroy Cobbley
See the city approved plans for location, with todays date, where sprinkler piping is ok to cover. As-builts are going to be required showing the pipe routing changes.
INSP-Sprinkler Rough-in1/12/20111/13/20111/13/2011APASS
DetailsTroy Cobbley
The piping in the main/front canopy can be covered. See the city approved plans for location with todays date.
INSP-Sprinkler Rough-in1/6/20111/7/20111/7/2011APASS
DetailsTroy Cobbley
See the city approved plans for the location where the sprinkler piping can be covered. It is marked with todays date.
INSP-Sprinkler Rough-in1/6/20111/6/20111/6/2011PCANC
DetailsTroy Cobbley
To be cancelled per Don Forrester ###-####