Permit Number | FIR10-00641 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
11311 W CHINDEN BLVD
|
Project Name | HP BLDG 5 LWR LVL FOCUS ROOMS |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide three strobes and connect them to the existing NAC circuit in the area to accomodate a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-02446 Hewlett Packard-Building 5 1st & 2nd floor- Permit for minor tenant improvements to existing spaces on the first and second floors of building #5 with work to include the removal of misc. interior non bearing partition walls and the construction of new non-bearing partition walls and associated electrical, plumbing and mechanical for a break room and small focus room per the approved plans. This is a fully sprinklered building:any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
|