Permit Information
Permit NumberFIR11-00024
StatusFinaled
Name PEAK ALARM
Site Address 623 S AMERICANA BLVD
Project NameOEC AMERICANA
Customer Number 
ePlanReviewNo
Description
2-1-11: PLAN MODIFICATION (6 initiating devices affected)– this plan modification is to include previously excluded devices for HVAC monitoring/shutdown, revised plans and documents for the appropriate Fireman’s Hat Light in elevator recall functions, and incorporate a field change that adds monitoring of a PIV.
1-25-11:
This fire alarm permit is to replace the existing fire alarm system. The system will monitor sprinkler system devices and perform elevator recall/shunt trip functions. No HVAC is shown as being part of this permit scope of work. If HVAC shutdown is required/provided, a plan modification shall be required.
Associated building permit: BLD10-01564 (OEC - OFFICE ENVIRONMENT COMPANY - AMERICANA) This building is required to be fire sprinklered for building area increase, for story increase, and for fire area. To remodel an existing building for a new retail sales and warehouse tenant. After the remodel, this building will have a 16,814 square foot 1st story and a 3,860 square foot 2nd story. Work is to include a single user restroom accessible to the disabled, a roll-in-type shower and a locker room accessible to the disabled, a new stairway to serve the 2nd story, a new floor structure next to the new stairway, new exterior walls, exterior windows, exterior doors, interior walls, interior wall infills, and interior finishes. This permit also includes removing about 11,500 square feet of the floor of the existing 2nd story and demolishing and rebuilding the long narrow section of building parallel to and adjacent to Americana Boulevard. Structural work includes new openings in existing masonry walls, shear walls, bearing walls, window headers, roof joists, column splice connections, and pilaster patching. This permit does NOT include the installation of storage racks. A separate permit for high rack storage is required. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. Planning approval done under DRH10-00142. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/2/20112/2/20112/2/2011PPASS
DetailsForrest France
Corrections field verified for completion. Fire alarm work passed final inspection. Permit finaled.
INSP-Final Inspection1/27/20111/28/20111/28/2011AFAIL
DetailsForrest France
Noted items include: Provide plan modification resubmittals for added duct detectors at RTU's per review comments, elevator control functions test pending repair of shunt trip, RTU units 6 and 8 appear to have damaged relays at detector housings, missing inspectors test at the sprinkler system for the flow switch, post signage at the door to the FACP room per review note #22, provide points map at the panel.