Permit Information
Permit NumberFIR11-00096
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC BMAC IT RM PROGRAMMING
Customer Number 
ePlanReviewNo
Description
This quick permit is to re-program the FACP for a double interlock activation of the existing preaction system (previously activated by two smoke detectors, now it will be programed to activate upon a smoke detector and low-air signal). In addition, a control relay currently used to shut off the power to the computer room is to be deleted. This was previously a customer requested feature and is no longer desired. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/24/20156/26/20156/26/2015APASS
DetailsJim Page
Pre-action system tested, isolated low air alarm, no solenoid activation, isolated one smoke, no solenoid activated, activated low air with smoke, solenoid activated and tripped pre-action valve. Also tested alarm pressue switch as well as both tamper switches associated with this pre-action system.
FIR-Aging Inspection6/15/20156/15/20156/23/2015 NR
DetailsTroy Cobbley
I spoke with St Als Maintenance, John Mcademis, about the need to get this inspection performed.
INSP-Final Inspection6/22/20156/22/20156/22/2015PCANC
DetailsTroy Cobbley
I set up wrong inspection number
FIR-Aging Inspection4/29/20144/29/20145/7/2014 NR
DetailsTroy Cobbley
I spoke to Brian about getting this permit finaled
FIR-Aging Inspection5/31/20135/31/20136/4/2013 NR
DetailsTroy Cobbley
I spoke to Curtis at SimplexGrinnell and he is going to follow up with Charlie and Steve on the job status.
FIR-Aging Inspection1/21/20131/21/20131/24/2013 NR
DetailsTroy Cobbley
Brian with SimplexGrinnell is going to follow up on the project status.
FIR-Aging Inspection9/28/20129/28/201210/1/2012 NR
DetailsTroy Cobbley
Forwarded information to Scott for further action.
FIR-Aging Inspection3/20/20123/20/20123/20/2012 NR
DetailsTroy Cobbley
I spoke to Charlie with SimplexGrinnel and he stated he would follow up on this project.