Permit NumberFIR11-00120
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3858 N GARDEN CENTER WAY Unit: 201
Project NameDRJ DESIGN STE 201
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding three sprinklers due to new wall and ceiling configuration.


Building Department Scope:

(DRJ – Garden Plaza – Ste # 201) Permit is to build out for the first time a 368 square foot office space in an existing shell (Shell # BLD07-03134). Approval is contingent upon adhering to the approved plans on file. Work to include: construction of interior non-combustible full height partition walls to separate this space from the rest of the floor, new light switching, new accessible door / hardware, installation of ducts and diffusers, installation of new millwork, installation of new break room sink, and finishes in compliance with chapter 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**

Fire Sprinkler System Design/Spacing:

The existing system is a 3” x 3” x 1½” grid. The new sprinklers are being added on a one for one basis. Therefore, new hydraulics were not necessary.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/22/20114/25/20114/25/2011APASS
DetailsTroy Cobbley
Permit finaled. Per Cam the head legend on the drawings does include a type error for the sprinkler SIN. The correct pendants have been installed.
INSP-Sprinkler Rough-in4/12/20114/13/20114/13/2011PPASS
DetailsTroy Cobbley
piping is ok to cover. The wrong pendants have been installed per the SIN in the head legend. It appears to be a type error.