Permit Number | FIR11-00134 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
3295 W ELDER ST
|
Project Name | Wells Fargo Restroom Remodel |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to relocate an existing strobe and increase its candela rating from 15cd to 30cd. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-01739 (WELLS FAGO - 1st Floor Restroom Remodel) Permit is to remodel the existing restrooms on the first floor. Approval contingent upon adhering to the approved plans on file. Work to include: construction of interior non-bearing (non-combustable) walls to create new entries into the restrooms, installation of new bathroom partitions in the women's restroom, installation of new plumbing fixtures, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
|