Permit Information
Permit NumberFIR11-00153
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 3 OASIS Area.
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide two new strobes and connect them to the existing fire alarm system. There are redlines on the plans regarding potential inadequate visual coverage. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector
Associated building permit: BLD11-00172 To remodel a 1838 sq/ft existing office area By demoing out old office partition walls and installing new ones and modifing acoustical ceiling.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/14/20116/16/20116/16/2011APASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection6/14/20116/16/20116/16/2011APASS
DetailsForrest France
Fire alarm work passed functional test.
INSP-Alarm Testing6/15/20116/15/20116/15/2011APART
DetailsForrest France
Functional test scheduled 6/16
INSP-Conference6/14/20116/14/20116/14/2011PDONE
DetailsForrest France
Regarding after hours inspection schedule.