Permit Information
Permit NumberFIR11-00208
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 6146 W CORPORAL LN
Project NameINTEGRATED ANALYTICAL SOLUTION
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a manual and automatic detection system that is not required by IFC however has been requested by the owner. The panel is a combination fire alarm/burglar alarm panel with signals being transmitted via an AES RF radio w/ IntelliTap instead of a DACT reporting system. This permit scope shall include a pull station at the tenant entrance, a remote annunciator, automatic detection throughout the tenant space, and notification throughout. HVAC monitoring/shutdown was not indicated on the plans. If duct detectors are provided/required, a plan modification shall be required to connect them to the fire alarm panel. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/2/20119/6/20119/6/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/13/20117/15/20117/15/2011APART
DetailsForrest France
Fire alarm testing completed satisfactory- Final pending provision for item #28 on the fire code review comments regarding a knox box per BMC requirements.
INSP-Sprinkler Rough-in/Hydro6/28/20116/29/20116/28/2011PCANC
DetailsTroy Cobbley
>> Inspection requested via web by Alicia Pauley Inspection cancelled from web by: Alicia Pauley