Permit Information
Permit NumberFIR11-00215
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 3019 N COLE RD
Project NameSockeye Grill Hood
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/1/20122/6/20122/6/2012APASS
DetailsTroy Cobbley
Permit finaled. Suppression system functioned correctly.
INSP-Final Inspection1/23/20121/24/20121/24/2012ACANC
DetailsTroy Cobbley
Canceled per phone conversation with Alex Phone #: ###-####
INSP-Final Inspection1/17/20121/18/20121/18/2012AFAIL
DetailsTroy Cobbley
No body was at the job site at the 8:00 agreed time. I waited until 8:15. Could not make contact with the contractor so I left message and moved on. No inspection was performed.
INSP-Final Inspection1/13/20121/17/20121/17/2012ACANC
DetailsTroy Cobbley
mary Phone #: ###-#### To be rescheduled for tomorrow.
INSP-Conference1/12/20121/12/20121/12/2012PDONE
DetailsTroy Cobbley
I stopped at the job site and spoke to a gentleman named Zack. He showed me that all requirements by the mechanical inspector had been met. I called Mary at Taylor Brothers and let her know that we are ready for an inspection. She stated that she will try to get something scheduled for next week.
INSP-Final Inspection5/27/20116/1/20116/1/2011AFAIL
DetailsTroy Cobbley
Manual pull station was mounted too high but was modified while I waited. The location of the three fryers do not .meet the requirements of IMC 507.12. Plans did not match the actual appliance layout. No testing was performed.
INSP-Final Inspection5/26/20115/27/20115/27/2011ACANC
DetailsTroy Cobbley
To be canceled per phone conversation with Mary. Also per phone conversation with Jerry McAdams with the Boise Fire Dept. the manual pull station is required to meet current code requirements for spacing from the hood. It is currently located less than 10' from the hood. No actual inspection has been performed at this project.
INSP-Final Inspection5/26/20115/26/20115/26/2011PCANC
DetailsTroy Cobbley
Cancelled due to time constraints. Mary will reschedule for tomorrow.
INSP-Final Inspection5/23/20115/26/20115/26/2011AFAIL
DetailsTroy Cobbley
Arrived on site and found two nozzles missing and per Mary with Taylor Brothers the technician went to a different job. She would like to reschedule for later today.