Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR11-00220
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 10792 W FRANKLIN RD
Project NameIDAHO POWER M&E SHOPS
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide a 4-wire horn/strobe and connect it to an existing circuit due to a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-00366 (IDAHO POWER – M & E Shops) Permit is to remodel an existing 768 business area by dividing it and creating two business areas. Approval contingent upon adhering to the approved plans on file and attached plan review report. Work to include: construction of new non-combustible full height partition wall, new light switching, new accessible door / hardware, and finishes in compliance with chapter 8 of the 2006 IBC. This building is not fire sprinklered. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/8/20118/9/20118/9/2011PPASS
DetailsTroy Cobbley
permit finaled