Permit Number | FIR11-00220 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
10792 W FRANKLIN RD
|
Project Name | IDAHO POWER M&E SHOPS |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide a 4-wire horn/strobe and connect it to an existing circuit due to a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-00366 (IDAHO POWER – M & E Shops) Permit is to remodel an existing 768 business area by dividing it and creating two business areas. Approval contingent upon adhering to the approved plans on file and attached plan review report. Work to include: construction of new non-combustible full height partition wall, new light switching, new accessible door / hardware, and finishes in compliance with chapter 8 of the 2006 IBC. This building is not fire sprinklered. **TLW**
|