Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR11-00267
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 190 E BANNOCK ST
Project NameSLRMC SOILED UTILITY SMOKE DET
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide smoke detectors in all soiled utility rooms throughout the hospital. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/12/20119/13/20119/13/2011APASS
DetailsForrest France
Field verified repair of one notification device at the 1st floor elevator lobby. Fire alarm permit final approved.
INSP-Final Inspection9/6/20119/7/20119/13/2011APART
DetailsForrest France
Completed remainder of testing for the scope of permit work.
INSP-Alarm Testing9/12/20119/12/20119/12/2011PPART
DetailsForrest France
Remainder of the new SD at the basement and 1st floor levels tested okay. Final pending repair of one non-functional notification appliance at the 1st floor elevator lobby.
INSP-Final Inspection8/31/20119/1/20119/1/2011ADEFR
DetailsForrest France
scott - please call 45 minutes prior Phone #: ###-####
INSP-Final Inspection8/16/20118/17/20118/17/2011APART
DetailsForrest France
Tested new smoke detection at the 3rd floor east and south towers and 2nd floor central and north floor areas. Reinspected door holders at the 5th floor for functionality after repairs.
INSP-Final Inspection8/15/20118/16/20118/16/2011PDEFR
DetailsForrest France
scott Phone #: ###-####
INSP-Final Inspection8/2/20118/3/20118/3/2011APART
DetailsForrest France
Site testing completed for new smoke detectors at the 8th, 7th, 6th and 5th floors. Descriptor at address 78 (5th) to accurately indicate the room located. Noted door holds at the 5th floor did not release upon fire alarm activation. Discussed inspection schedule for the remainder of the project.
INSP-Conference7/28/20117/28/20117/28/2011PDONE
DetailsForrest France
Regarding project inspection schedule.