Permit Information
Permit NumberFIR11-00388
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 300 E JEFFERSON ST
Project NameJMOP ELEVATOR HEAT/SMOKE
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide a new heat detector at the top of one elevator shaft, relocate an existing heat detector in the other elevator shaft, relocate a heat detector to be within 2ft of a sprinkler heat in the elvator machine room, and to add a new smoke detector for elevator recall functions in the elevator machine room. Per the contractor, there is no capablility for the elevator to perform fireman's hat light functions. The alarm matrix appears to have accurate elevator functions shown. Inspector to field verify. If the elvator has a fireman's hat light, a plan modification shall be required to include the hat light functions. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/14/201112/15/201112/16/2011APASS
DetailsForrest France
Per state elevator inspector, car installed prior to flashing hat requirement. Permit finaled.
INSP-Final Inspection10/18/201110/18/201110/18/2011PPEND
DetailsForrest France
Final pending elevator hat functions.
INSP-Final Inspection9/20/20119/21/20119/21/2011PNR
DetailsForrest France
INSP-Alarm Testing9/16/20119/21/20119/21/2011AFAIL
DetailsForrest France
The elevator car is equipped with a firemans hat light. Per ANSI/ASME 2.27.3.2.6 the visual signal shall illuminate intermittently upon machine room or hoistway device activation. See review notes and project description for details regarding requirements for a plan modification.