Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR11-00405
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Cooking hood
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/201110/31/201110/31/2011PPASS
DetailsTroy Cobbley
The hood suppression system functioned correctly. Permit finaled.
INSP-Final Inspection10/26/201110/27/201110/27/2011AFAIL
DetailsTroy Cobbley
The pizza oven suppression system can be finaled when the paper work is signed. Per the IMC commentary this type of oven can be installed under a type II hood so the duct/plenum nozzles are adequate. The other supression system, when activated, did not turn off the under hood lights. So it will need to be retested once the wiring has been corrected.