Permit NumberFIR11-00414
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 517 N 13TH ST
Project NameNEWHOUSE APARTMENTS
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of a new 13R antifreeze sprinkler system for six apartments. The two systems will have antifreeze protection (48% glycerin) down to a -16. Premix solution is required. The risers are located in an exterior room with exterior access. The underground is 6” to the property line and then 4”x31’ of C-900. There is no meter since this is a dedicated fire protection supply. There is a 2” RP backflow preventer with 2” SCH 40 steel risers and CPVC telescoping branch piping. The extended coverage sprinklers are spaced at 20’x20’



Building Department Scope:

(NEWHOUSE APARTMENTS) (517-519 N 13th St) Scope of work demolition of two small apartments & foundations, compaction under special inspection of soils for bearing per geotech report and includes all associated site work shown on plans, submitted for review and approved by applicable reviewing agencies. To construct a 3,804 sq. ft., 2-story, 6 unit, Type VB wood frame construction, R-2 Occupancy Group Apartment building. Units "A, B, D & E" are 542 sq. ft. and ADA unit and "C" unit are 521 sq. ft. All ground floor units to comply as Type "B" accessible units served by an accessible route to, into and throughout unit. Building is fully sprinkler with 13R system. 1-hour fire-resistive separation required between dwelling units vertically and horizontally .drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/27/201112/27/201112/27/2011PPASS
DetailsForrest France
Repair completed, final inspection and testing passed. Fire sprinkler permit finaled.
INSP-Final Inspection12/22/201112/23/201112/23/2011APART
DetailsForrest France
Final walkthrough completed acceptable. Final pending repair of the flow switch at system #2.
INSP-Final Inspection12/1/201112/2/201112/1/2011PCANC
DetailsForrest France
Call Doug Funk at above # 30 minutes prior to inspection Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in/Hydro10/19/201110/20/201110/20/2011PPART
DetailsForrest France
2nd floor hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro10/18/201110/19/201110/19/2011PPART
DetailsForrest France
1st floor hydrostatic testing passed. 2nd floor test failed due to pressure loss at the guage and visible leakage at the system side of the riser manifold.
INSP-Sprinkler Rough-in/Hydro10/12/201110/13/201110/13/2011AFAIL
DetailsTroy Cobbley
The overhead hydro tests on both systems failed.
INSP-Sprinkler Rough-in/Hydro10/12/201110/12/201110/12/2011PCANC
DetailsTroy Cobbley
Cancelled. Overbooked - rescheduled for tomorrow.
INSP-Sprinkler Rough-in10/7/201110/7/201110/7/2011PPART
DetailsForrest France
Verified corrections, overhead work approved for cover.
INSP-Sprinkler Rough-in10/6/201110/7/201110/7/2011AFAIL
DetailsForrest France
Overspaced head at the 2nd floor, one pendent head at the 2nd floor and three pendent heads at the 1st floor are too close to light fixture junction boxes.
INSP-Sprinkler Rough-in10/5/201110/6/201110/6/2011PCANC
DetailsForrest France
overbooked
INSP-Sprinkler Rough-in10/4/201110/5/201110/5/2011APART
DetailsForrest France
UG fire supply line flush completed satisfactory.
INSP-Conference10/4/201110/4/201110/4/2011PDONE
DetailsForrest France
Regarding UG flushing schedule.
INSP-Sprinkler Rough-in/Hydro9/29/20119/30/20119/30/2011PPASS
DetailsForrest France
UG fire supply line hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro9/27/20119/28/20119/28/2011ANR
DetailsForrest France
ug r/i hydro//Brian Phone #: ###-####
INSP-Sprinkler Rough-in9/7/20119/8/20119/8/2011PPART
DetailsForrest France
Remainder of the UG fire supply line to the point of connection at the property line approved for cover.
INSP-Sprinkler Rough-in9/7/20119/7/20119/7/2011PCANC
DetailsForrest France
ug cover//Brian Phone #: ###-#### Inspection cancelled from web by: Barbara Stitt
INSP-Sprinkler Rough-in8/31/20118/31/20118/31/2011PPART
DetailsForrest France
UG fire supply line IBR only okayed for cover.