Permit Information
Permit NumberFIR11-00423
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N MILWAUKEE AVE Unit: 1047
Project NameBTS - #1047 Bohme
Customer Number 
ePlanReviewNo
Description
Quick Permit
Add, relocate and plug sprinklers to accommodate new wall and ceiling construction for a new tenant.
(BOHME – Boise Towne Square – Space # 1047) To remodel an existing 2,500 square feet retail tenant space for a new retail tenant. Work to include: [installation of interior non-bearing partition walls to create, a storageroom, a sales area, back entry, and 7 fitting rooms], installation of new flooring throughout, construction of a new storefront system, installation of suspended ceiling system per ESR-1289, new lighting, and interior finishes in compliance with ch. 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department, The smoke evacuation system shall remain operational as originally installed under the 1985 UBC. The design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks; all racks that exceed 8 ft. must be submitted separately for permit. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/17/201110/17/201110/17/2011PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in9/15/20119/15/20119/15/2011PPASS
DetailsTroy Cobbley
Corrections have been made and six additional uprights have been added over the retail area
INSP-Sprinkler Rough-in9/12/20119/13/20119/13/2011APASS
DetailsTroy Cobbley
Piping can be covered but access will need to be provided to verify that the hanger was repaired. Also the pendant head near the rear exit needs to be relocated closer to the edge of the soffit as discussed. This can be verified at the final.
INSP-Sprinkler Rough-in9/12/20119/12/20119/12/2011PCANC
DetailsTroy Cobbley
overbooked