Permit Number | FIR11-00468 |
Status | Finaled |
Name |
FIRE SENTRY SYSTEMS
|
Site Address |
4017 W OVERLAND RD
|
Project Name | BIOMAT USA |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide two new horn/strobes and two new smoke detectors due to two new restrooms being built. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments (see redlined plans). Associated building permit: BLD11-01750 (BIOMAT USA) Permit is to remodel an existing 9,098 sq. ft. office tenant by combining with the adjacent 2,028 square foot tenant space to create a 11,548 sq.ft. space. This building is sprinklered for building area increase. Approval contingent upon adhering to the approved plans on file. Work to include: installation of new non-rated walls to create separate sex accessible restrooms and to expand the waiting room, minor demolition, new plumbing, and interior finishes in accordance with Ch. 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire department. **TLW**
|