Permit Number | FIR11-00625 |
Status | Finaled |
Name |
NORTHWEST SALES COMPANY
|
Site Address |
950 W BANNOCK ST Unit: 270
|
Project Name | BROWN & CALDWELL SUITE 270 |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to relocate existing notification devices to accomodate a tenant remodel. Device candela ratings and circuiting to remain the same. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-02559 (Brown & Caldwell ) remodel suite 270 for tenant add new nordwall partitions to reconfigure space.
|