Permit Number | FIR11-00658 |
Status | Finaled |
Name |
MICRON TECHNOLOGY INC FP
|
Site Address |
8000 S FEDERAL WAY
|
Project Name | B50-R&D EXPANSION BLD |
Customer Number | |
ePlanReview | No |
Description |
The Fire Sprinkler Scope of work consists of providing a 6 nozzle deluge water curtain to protect opening in a 3 hour wall. The design is somewhat based on FM data sheet 1-23. The detection is from cross-zoned smoke and heat detector. There are two systems. The other side of the wall is in a different permit. The system will actuate on the opposite of the wall of where the detectors have initiated. The design has been reviewed by both the Fire Marshal and Building Official.
Note: See permit FIR11-00301, FIR11-00365, FIR11-0431, FIR11-00448, FIR11-00524, FIR11-00645 for the review on other portions of this building
|