Permit Number | FIR11-00660 |
Status | Finaled |
Name |
ENTERPRISE ELECTRIC
|
Site Address |
1620 W RIVER ST
|
Project Name | INTERFAITH SANCTUARY |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to relocate three existing notification devices and one existing pull station. No circuiting changes have been indicated, therefore new battery calculations and voltage drops are not required. The minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. The mounting height for manual pull stations shall be a minimum of 42 inches and a maximum of 48 inches measured vertically, from the floor level to the activating handle or lever of the box. 2009 IFC 907.5.2.2. There are no written review comments. Associated building permit: BLD11-00507 (INTERFAITH SANCTUARY HOUSING-MENS RESTROOM UPGRADE) Remodel to continue phased construction program for work required under an existing Upgrade Agreement (see BLD08-02236) on file. This phase to include upgrading the Men's restroom to current accessibility standards; create rooms designated as future shower and unisex restroom with perimeter walls and installing rough-in plumbing lines for future fixtures; change out existing 5 ton RTU with a new 4 ton unit connected to existing ductwork; added new walls re-define previous proposed sleeping areas to become Administration & Hospitality Rooms. Sleeping Unit #1-Single Men will be slightly increased in size and existing Sleeping Room 109A indicated for use for 6 residents will be reduced in size, all as indicated on reviewed plans. The scope of this permit will begin providing compliance for a portion of Phase 4 as indicated in upgrade agreement on file. NOTE: This building is fully fire sprinklered in accordance with requirements for "R" occupancy fire areas per Ch. 9, 2006 IBC. drs
|