Permit NumberFIR12-00025
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 9465 W EMERALD ST Unit: 110
Project NameLIBERTY MUTUAL – VIDEO EYE BUI
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to remove existing Gentex notification in the tenant space and replace them with System Sensor devices to match the rest of the existing building. The new devices will remain on the same circuit (NAC7) as the ones being replaced. Three new duct detectors are being provided to existing zone #11.

Associated building permit: BLD11-02749 (LIBERTY MUTUAL) Remodel an existing 2,650 sq. ft. office area (formerly Starbucks) in combination with removal of interior wall to expand new office for Liberty Mutual into adjoing vacant tenant space adding 1,073 sq. ft. for a total area 3,723 sq. ft. office tenant on the first floor of an existing building per approved plans. This permit is attached to the same set of plans used to create permit BLD11-02750 reducing the existing vacant tenant space area to approximately 1,908 sq. ft. vanilla finish space being created by the expansion for Liberty Mutual. Work to include select interior demolition; construction of new 29.5 ft. by full height wall to separate tenant spaces; construct interior non-bearing walls to create reception area, conference / small meeting / break / mail / storage / telecom / private office rooms; S.A.T. ceiling grid, bracing, new /relocated luminaries and mechanical fixtures; interior cabinetry, floor and wall finishes; interior access/egress doors, frames and hardware; modifications to electrical, plumbing, mechanical, sprinkler & alarm systems. Redline notes on approved plans and all attached plan review comments of all reviewing agencies are part of the approved plans requiring compliance. NOTE: This building is fully fire sprinklered to take advantage of special code allowances when sprinklers are provided (non-rated corridor, exit separation reduction, openings between floors, etc.). drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/2/20122/6/20122/6/2012APASS
DetailsTroy Cobbley
Permit finaled. I found two strobes that were overspaced that were relocated as I waited. Also the sample tubes in one of the three duct smoke detectors had been installed backwards. THis was also corrected as I waited.