Permit Information
Permit NumberFIR12-00099
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project NameB50-R&D EAST EXPANSION BLD
Customer NumberC15044
ePlanReviewNo
Description
Fire Alarm System: C15044 This scope of work covers the addition to a fire alarm system previously submitted under FIR11-00575. This permit covers devices primarily installed in the east-half (second half)of the cleanroom in the new R and D Fab permitted under BLD11-00818. The remainder of the fire alarm system including the deluge system and chemical room are covered under separate permits.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/18/20129/18/20129/18/2012APASS
DetailsForrest France
Scope of fire alarm work completed, inspections passed. Permit final approved.
INSP-Alarm Testing8/15/20128/15/20128/15/2012APART
DetailsForrest France
Items tested today include MP stations at the fan deck, SD above the mechanical deck NAC, duct detectors at the electrical rooms.
INSP-Alarm Testing8/1/20128/1/20128/2/2012APART
DetailsForrest France
System components tested today include vesda zones 8,9,10,11 and 12, added a/v at the SE fab exit, FP system #11 tamper and flow switch, verified outside bell function.
INSP-Alarm Testing7/18/20127/19/20127/19/2012PPART
DetailsForrest France
Completed testing for MAU shutdown at zones 8,9,10,11, and 12.
INSP-Alarm Testing7/18/20127/18/20127/18/2012PPART
DetailsForrest France
Completed functional testing and walkthrough of occupant notification at the sub fab, fab, electrical, mechanical, and fan deck areas. One location SE first floor adjacent to the exit enclosure appears lacking in visual coverage.
INSP-Alarm Testing7/17/20127/17/20127/17/2012PPART
DetailsForrest France
Completed testing for underfloor SD at zones 8,9,10,11, and 12. Also tested MP stations at the sub fab, first floor electrical, exit stairs, and fire riser rooms. SE riser tampers and flows on systems 5,6, and 9 also tested okay. System 11, MAU's, and second floor initiating devices are not yet ready for inspection. Discussed schedule for notification testing at the clean room fab area.