Permit Number | FIR12-00107 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
11311 W CHINDEN BLVD
|
Project Name | HP B7 Focus Rooms |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to add two new strobe only devices into two new focus rooms. There are redlines on the plans to add notification due to an area no longer covered by existing devices. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD12-00224 (HEWLETT PACKARD)(BLDG B7 - FOCUS ROOMS) Remodel an existing area on the first floor of B7 to create (4) focus rooms. Total area of remodel 248 sq.ft
|