Permit Information
Permit NumberFIR12-00159
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 782 S AMERICANA BLVD
Project NameSummit Dental Office
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new fire alarm control panel for sprinkler system monitoring and HVAC shutdown/monitoring. This permit scope of work includes a remote annunciator panel, a smoke detector above the FACP, a pull station, duct detectors for HVAC shutdown, and zones to monitor the dry and wet sprinkler system valves.
Associated building permit: BLD11-01743
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/12/20127/12/20127/13/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing7/11/20127/12/20127/12/2012AFAIL
DetailsTroy Cobbley
All times tested except there are issues with the duct smoke detectors. The first duct detector found and tested shut the hvac unit down but came in as the wrong zone. The second duct smoke detector found could not be tested due to the hvac unit not staying operational. The remaining two duct smoke detectors locations are not readily known nor is their controlling thermistats.