INSP-Final Inspection | 10/9/2012 | 10/10/2012 | 10/10/2012 | P | PASS |
Forrest France
|
|
|
Final inspection and walkthrough passed. Forward flow completed okay.
|
INSP-Final Inspection | 10/4/2012 | 10/9/2012 | 10/9/2012 | P | PART |
Forrest France
|
|
|
Final pending satisfactory forward flow test. 2" drain test did not provide adequate gpm.
|
INSP-Final Inspection | 9/21/2012 | 9/24/2012 | 9/24/2012 | A | FAIL |
Troy Cobbley
|
|
|
Permit is not ready for a final inspection. The alarm initiating devices have not been tested, ceiling tile has not been installed, wood has been installed above the ceiling at the pharmacy security door/track and an upright sprinkler head at the main exit is covered in tape.
|
INSP-Sprinkler Rough-in | 8/27/2012 | 8/27/2012 | 8/27/2012 | P | PART |
Forrest France
|
|
|
Overhead rough-in inspections passed.
|
INSP-Sprinkler Rough-in/Hydro | 8/15/2012 | 8/15/2012 | 8/15/2012 | P | PART |
Forrest France
|
|
|
Hydrostatic test of the new overhead wet system passed.
|
INSP-Sprinkler Rough-in | 8/10/2012 | 8/10/2012 | 8/10/2012 | A | PART |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in | 6/12/2012 | 6/12/2012 | 6/12/2012 | A | PART |
Forrest France
|
|
|
Added coverage at the mens restroom okayed.
|
INSP-Sprinkler Rough-in | 6/11/2012 | 6/11/2012 | 6/12/2012 | P | PART |
Forrest France
|
|
|
Overhead rough-in inspection completed. Noted obstruction at ductwork >4' one location, exposed wood at the pharmacy accordian door pocket to be protected or verified for min. combustibility. Coverage at the men's restroom to be adjusted due to light fixture obstruction, FDC and dry pendent heads in the coolers are not yet installed.
|