Permit Information
Permit NumberFIR12-00229
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 3113 N COLE RD
Project NameBUSINESS MALL NORTH CANOPY
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding protection to a portion of a canopy. The existing dry system will be extended. The design criteria is Ordinary Hazard Group I. Therefore, sidewalk sales are NOT permitted. Extended coverage sprinklers are being utilized based on 16’x16’ spacing.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/10/201210/10/201210/10/2012PPASS
DetailsTroy Cobbley
Permit finaled. The annual inspection has just expired but Don with Curtis Fire has been contracted to do the new inspection. He will call me when completed.
FIR-Aging Inspection10/2/201210/2/201210/10/2012 NR
DetailsTroy Cobbley
I spoke to Don and he is going to get the project scheduled for a final.
INSP-Sprinkler Rough-in/Hydro5/14/20125/14/20125/14/2012PPASS
DetailsTroy Cobbley
Overhead hydro test for the new piping passed. Witnessed gain in pressure. Piping can be covered.
INSP-Sprinkler Rough-in/Hydro5/11/20125/11/20125/11/2012PPART
DetailsTroy Cobbley
Project was not ready for hydro test but the sprinkler rough-in passed.