Permit Number | FIR12-00273 |
Status | Finaled |
Name |
NORTHWEST SALES COMPANY
|
Site Address |
8854 W EMERALD ST Unit: 270
|
Project Name | Smiles, Inc-W.Boise Prof. Cntr |
Customer Number | |
ePlanReview | No |
Description |
This fire alarm quick permit is to increase the candela ratings of two existing notification devices to accomodate a tentant remodel. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD12-00923
|