INSP-Final Inspection | 8/16/2012 | 8/17/2012 | 8/17/2012 | A | PASS |
Forrest France
|
|
|
Remainder of fire alarm work passed functional testing. Permit finaled.
|
INSP-Final Inspection | 8/16/2012 | 8/16/2012 | 8/16/2012 | P | CANC |
Troy Cobbley
|
|
|
Overbooked. Spoke to Rand about rescheduling.
|
INSP-Sprinkler Rough-in/Hydro | 8/14/2012 | 8/15/2012 | 8/15/2012 | A | FAIL |
Troy Cobbley
|
|
|
Verified correct panel, battery size, phone lines 1 and 2 and sprinkler flow switch function. Also verified the smoke detector and audio/visual spacing. Stopped inspection after testing a bedroom smoke detector and it activated all of the notification devices which is not allowed. Also the facp needs to be connected to the tamper switches as shown on the approved drawings.
|
INSP-Final Inspection | 8/10/2012 | 8/13/2012 | 8/13/2012 | A | FAIL |
Troy Cobbley
|
|
|
The underground water supply has been turned off so no testing can be completed.
|
INSP-Final Inspection | 8/10/2012 | 8/10/2012 | 8/10/2012 | P | CANC |
Troy Cobbley
|
|
|
Rand Gruber Phone #: ###-#### >> Inspection requested via web by Rand D. Gruber Inspection cancelled from web by: Rand D. Gruber
|