Permit Information
Permit NumberFIR12-00393
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 1609 S OWYHEE ST
Project NameWhitney Elemetary Classroom Ad
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of adding above and below protection for the extension of two existing wings. The fire protection will be supplied from the existing 3” mains. Two new 2” feed mains will supply the extension of the two wings.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/26/201210/29/201210/29/2012APASS
DetailsForrest France
Coverage adjustments verified. Fire sprinkler permit work complete, permit finaled.
INSP-Final Inspection10/23/201210/23/201210/23/2012PFAIL
DetailsForrest France
Overspaced pendent coverage at three classrooms. Previous C/N items dated 10/5 verified for completion.
INSP-Sprinkler Rough-in10/4/201210/5/201210/5/2012AFAIL
DetailsTroy Cobbley
Provide "job site copy" city approved plans for inspection, three upright heads on two lines (six total heads) are blocked by truss webbing, branchline restraint is missing, earthquake bracing is missing, wrong extended coverage pendants have been installed which will require a plan modification, as-builts will atleast be needed to show the pipe routing changes, one upright head at the mezzanine walkway appears to be overspaced. Ceiling tile can be installed since items needing correction can be viewed from the mechanical walkway.