Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR12-00417
StatusFinaled
Name JBL FIRE PROTECTION LLC
Site Address 1405 S GOLDKING WAY
Project NameUnion Square Apartments Bld 9
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a new three floor apartment building per NFPA 13R. The system is supplied with floor level control valves, 1½” FDC and a 2” Backflow Preventer.

The underground is under permit FIR12-00247
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/22/20132/26/20132/26/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/20/20132/22/20132/22/2013ACANC
DetailsTim Frost
*Re-assingned by Scott Arellano*

Jonothan Lee Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro11/1/201211/5/201211/5/2012APASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in10/24/201210/24/201210/24/2012PPASS
DetailsTroy Cobbley
Tenting has been repaired and the batt insulation installed on the vertical rises. Piping can be covered.
INSP-Sprinkler Rough-in10/18/201210/19/201210/19/2012AFAIL
DetailsTroy Cobbley
I stopped at the job site and found that the tenting had not been repaired or the batt insulation installed.
INSP-Sprinkler Rough-in10/18/201210/18/201210/18/2012PPART
DetailsTroy Cobbley
The heat tape was ok but can not give an approval for cover due to the tenting not being completed in many locations. I also need the batt insulation installed at the vertical risers prior to an approval for cover being given.
INSP-Sprinkler Rough-in9/28/201210/1/201210/1/2012APART
DetailsTroy Cobbley
First and second floor sprinkler rough-in passed. One pendant was missing on the second floor but can be verified at the next rough-in inspection. Third floor hydraulic calculations need to be re-verified due to pipe routing changes in the remote area. Also tenting has not been done for the third floor or any of the heat trace tape. First and second floor piping can be covered except for the areas where heat trace will need to be inspected.