Permit Information
Permit NumberFIR12-00427
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 7210 W BARRISTER DR
Project NameADA COUNTY JAIL POD D
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a two level prison. The system makes extensive use of horizontal institutional sidewall sprinklers.

The fire protection underground piping was reviewed under permit FIR12-00363.

Plan Mod #1 – 2/07/2013
Conversion from a double interlock preaction system to a wet system.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/6/20136/7/20136/7/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection6/5/20136/6/20136/6/2013AFAIL
DetailsTroy Cobbley
Forward flush verification is needed and the PIV tamper switch needs to be adjusted.
INSP-Final Inspection4/24/20134/25/20134/25/2013PFAIL
DetailsTroy Cobbley
Still need to test the interconnection with the fire alarm control system, provide pressure relief vavle and submit on the work that was performed outside of the approved scope of work as requested last inspection.
INSP-Sprinkler Rough-in4/9/20134/10/20134/10/2013PPASS
DetailsTroy Cobbley
Upper level ceiling tile is ok to cover pipe. Work is being done outside of the scope of work shown on the drawings and will need to be submitted for review. It is protection in a small storage area.
INSP-Sprinkler Rough-in/Hydro3/27/20133/28/20133/28/2013PPASS
DetailsTroy Cobbley
This is for an overhead hydro. Please call Perly at ###-####. Overhead hydro passed visual guage inspection.
INSP-Sprinkler Rough-in3/14/20133/14/20133/14/2013PPASS
DetailsTroy Cobbley
Todays inspection was for the 1" supply line that is located in the vertical chase. It supplies water to the sidewall head in the Sally Port. Piping is ok to cover.
INSP-Sprinkler Rough-in3/6/20133/7/20133/7/2013APASS
DetailsTroy Cobbley
Upper level sprinkler piping above the hardlids is ok to cover. Piping above the lay in ceiling tile nt inspected yet due to t-bar not being installed yet.
INSP-Supply line flush2/28/20133/4/20133/4/2013APASS
DetailsTroy Cobbley
The underground supply line and the remote FDC supply line fludh passed
INSP-Sprinkler Rough-in/Hydro2/25/20132/25/20132/25/2013PPASS
DetailsTroy Cobbley
Underground hydro passed
INSP-Sprinkler Rough-in/Hydro2/21/20132/21/20132/21/2013PCANC
DetailsForrest France
Overbooked