Permit NumberFIR12-00442
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 100 E IDAHO ST
Project NameSt. Luke’s MSTI PEDS 1st Floor
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new NAC panel to accommodate new notification devices, smoke detectors, a manual pull station, and 3 in-duct detectors for damper shutdown to accommodate a tenant remodel.
Associated building permit: BLD12-01734
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/201310/18/201310/18/2013APASS
DetailsForrest France
Remainder of fire alarm work passed functional testing and inspection. Cd settings at two appliances adjusted while on site. Fire alarm permit approved for final.
INSP-Alarm Testing4/24/20134/26/20134/26/2013PPART
DetailsForrest France
Phase two fire alarm work as clouded and dated on approved plans passed functional testing.
INSP-Alarm Testing1/11/20131/14/20131/14/2013APART
DetailsForrest France
Notification, two dampers, and four SD in the areas as marked on approved plans passed functional testing today-
FIR-Aging Inspection11/27/201211/27/201211/27/2012 DONE
DetailsForrest France
Work in progress