Permit Information
Permit NumberFIR12-00477
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1477 S VINNELL WAY
Project NameCentury Landmark Center
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of a new tree system with 6” C-900 underground a 2½” backflow preventer, 2½” feed, 2½” cross main and 1½” branch piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/201211/8/201211/8/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/18/201210/22/201210/22/2012PFAIL
DetailsTroy Cobbley
The outside alarm bell has not been mounted yet therefore it could not be tested by the functional test of the flow switch. Forward flush passed.
INSP-Sprinkler Rough-in/Hydro9/26/20129/26/20129/26/2012PPASS
DetailsTroy Cobbley
Underground and overhead hydro tests passed.
INSP-Supply line flush9/26/20129/26/20129/26/2012PPASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Sprinkler Rough-in9/24/20129/24/20129/24/2012PPASS
DetailsTroy Cobbley
Sprinkler piping can be covered. Overhead rough-in for the exposed piping is passed. The approved plans indicate 155 dgree heads to be installed but 200 degree are actually installed, Per Tim Frost this change is acceptable but as-builts will be required prior to a final sign off.
INSP-Sprinkler Rough-in9/14/20129/17/20129/18/2012PPASS
DetailsTroy Cobbley
The cover inspection on the underground installation is passed. Piping can be covered.