Permit Information
Permit NumberFIR12-00494
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 350 N MILWAUKEE ST Unit: 117
Project NameH&M Clothiers
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of new tenant finish out for an existing space.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/16/201211/16/201211/16/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/13/201211/14/201211/14/2012AFAIL
DetailsTroy Cobbley
Prior to a final for this permit the ceiling and related pendant sprinkler protection needs to be installed in the two electrical rooms.
INSP-Sprinkler Rough-in11/13/201211/13/201211/13/2012PPASS
DetailsTroy Cobbley
See the city approved plans for locations where piping above lay-in ceiling tiles can be covered.
INSP-Sprinkler Rough-in10/23/201210/23/201210/23/2012PPASS
DetailsTroy Cobbley
ok to cover at the previously marked corrections
INSP-Sprinkler Rough-in10/18/201210/19/201210/19/2012APASS
DetailsTroy Cobbley
See the city approved plans for new locations where sprinkler piping can be covered. I also noted that a new wall located in the dressing room is now blocking a pendant head. It appears one pendant will need to be added and the pendant relocated to be more than 4" from the new wall. Also noted one pendant will be overspaced from the north side of the new entry vestibule when installed. Don and I agreed to add one pendant at this location.
INSP-Sprinkler Rough-in10/10/201210/10/201210/10/2012PPASS
DetailsTroy Cobbley
See the city approved plans for additional areas where the sprinkler piping can be covered.
INSP-Sprinkler Rough-in10/9/201210/9/201210/9/2012PPASS
DetailsTroy Cobbley
See the city approved plans for additional areas where sprinkler piping can be covered. Also see areas marked in blue that require corrections including the addtion of a sprinkler pendant in the window display.
INSP-Sprinkler Rough-in10/1/201210/1/201210/1/2012PPASS
DetailsTroy Cobbley
See the city approved plans for the location where sprinkler piping can be covered which has been clouded in red and given todays date. Also see adjacent location where three corrections will be required prior to a cover approval being given.
INSP-Sprinkler Rough-in9/25/20129/25/20129/25/2012PPASS
DetailsTroy Cobbley
See the city approved plans for the location where the sprinkler piping can be covered. It has been clouded and dated in red.