Permit NumberFIR12-00496
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 3210 E AMITY RD
Project NameDixon Container
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of adding sprinklers below overhead doors, converting the existing antifreeze system to a wet system by removing the antifreeze loop and connecting to the existing main, repair broken piping, replace damaged sprinklers and add one sprinkler to the compressor room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/201211/13/201211/13/2012PPASS
DetailsTroy Cobbley
Permit finaled. The rails for the overhead door have been removed.
INSP-Final Inspection10/12/201210/12/201210/12/2012PPART
DetailsForrest France
Scope of permit work completed and passed inspection with the exception of one overhead door at the northwest side yet to be deleted or protected by SW heads.