Permit Information
Permit NumberFIR12-00628
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 8551 W FRANKLIN RD
Project NameDemising Wall @ OfficeMax
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration. The provided owner’s certificate indicates that there will be no storage >12’. One new branch line will be added and connect to both mains of the grid. The existing pipe sizes are 4”x4”x1½”.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/24/20131/25/20131/25/2013PPASS
DetailsTroy Cobbley
Permit finaled. As-builts have been corrected and upright head changed out.
INSP-Final Inspection1/14/20131/16/20131/16/2013AFAIL
DetailsTroy Cobbley
The as-builts do not correctly show the actual branchline modified. Also many upright sprinkler heads are still covered with tape and one in the rear storage area has been painted.
INSP-Final Inspection1/9/20131/10/20131/10/2013AFAIL
DetailsTroy Cobbley
At the time of inspection the plans had not been resubmitted with the plan modifications. I did perform and pass the overhead hydro test.
INSP-Sprinkler Rough-in11/30/201211/30/201211/30/2012PPASS
DetailsTroy Cobbley
Could not find approved plans on site. Walls have been installed and the upright sprinkler protection appears to be correct. The two branchlines that were located too close to one another have been modified to increase spacing between the two lines. Painters had many of the heads covered so their removal will need to be verified at the final. Per the project history plans still have not been resubmitted for review and the hydro test is still needed. I left message on Stephen's cell phone to call me back.
INSP-Sprinkler Rough-in/Hydro11/6/201211/7/201211/7/2012PPART
DetailsTroy Cobbley
The plan review comments could not be located on site but per online documentation it appears a hydro test is required. I spoke to Stephen about this. I also noted two painted upright sprinkler heads. Their locations are marked on the plans. Also two branchlines, with sprinkler heads, are located less than 6'-0" from one another . On of them does not appear on the approved plans. Plans showing the actual pipe routing will need to be resubmitted and the spacing issue corrected. This list is not all inclusive since not all of the walls/work has been completed at this time.