Permit NumberFIR12-00698
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC ED EXPANSION
Customer Number 
ePlanReviewYes
Description
This fire alarm permit is to provide speaker/strobes (chime type) on the Central Tower portion of the addition and chime/strobes on the South Tower portion of the addition, smoke detectors, monitoring co2 gas, release of security doors upon alarm actuation, door holder/mag lock release, in-duct detectors w/ remote test switches for fire/smoke damper control, and remote annunciator panels at entrances and nurses’ stations.
Associated building permit: BLD12-01914
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/30/20149/30/20149/30/2014PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing7/1/20147/2/20147/2/2014APASS
DetailsTroy Cobbley
The fire alarm in Phase III (Med Lab) is complete.
INSP-Alarm Testing7/1/20147/1/20147/1/2014PDONE
DetailsTroy Cobbley
Need two fire smoke dampers adjusted. before sign off in the remodeled area.
INSP-Alarm Testing6/30/20146/30/20146/30/2014PDONE
DetailsTroy Cobbley
Additional area in the remodeled ER area passed. Need two smoke detectors relocated to the center line of the doors and with-in 5'
INSP-Alarm Testing5/14/20145/14/20145/14/2014APASS
DetailsTroy Cobbley
Fire alarm devices in the temporary corridor in the remodeled ER area have been tested and passed
INSP-Alarm Testing5/7/20145/8/20145/8/2014APART
DetailsTroy Cobbley
Inspection was for temporary corridor through the ER area. All items tested ok but one additional notification device is needed at the east end bdfore I can give an "ok" for use.
INSP-Alarm Testing12/26/201312/27/201312/27/2013APART
DetailsTroy Cobbley
Fire alarm complete in 2B and Staff Lounge.
INSP-Alarm Testing9/6/20139/9/20139/9/2013ADONE
DetailsCraig D. Hanson
Phase 2A; All systems tested and pass for this phase. Initiating devices + 4 pull stations and 1 duct detector.
INSP-Alarm Testing9/6/20139/6/20139/6/2013PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Friday, September 06, 2013.
INSP-Alarm Testing3/7/20133/8/20133/8/2013ADONE
DetailsTroy Cobbley
Phase one fire alarm passed. Door release has been corrected and a weather proof device added in the "decontam" room. Brian is going to keep the updated as-builts on his Ipad.
INSP-Alarm Testing3/5/20133/6/20133/7/2013PPART
DetailsForrest France
Functional testing and inspection for fire alarm work in "phase one" completed. Noted items include; provide a WP notification appliance in the decontamination room, address at SD's for door release (22 &23) are switched, SD and ID at the south set of hallway doors between phase one and two are not yet installed, ID M8-13 has been relocated to the main corridor beyond phase one, delayed egress provisions at the secured doors must meet conditions per IFC 2009, record drawings and panel maps to match field modifications including device locations and addressing. Chimes/strobes, MP at the nurses station, SD and ID(except as noted) tested okay. *Inspection completed 3/6/13 PM*.