Permit NumberFIR13-00208
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 3501 W ELDER ST Unit: 100
Project NameCore Engineering
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide notification and re-locate existing notification to accomodate a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD13-00862.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/15/20135/16/20135/16/2013APASS
DetailsForrest France
Inspection passed. Fire alarm permit finaled.
INSP-Alarm Testing5/14/20135/15/20135/15/2013APASS
DetailsForrest France
Fire alarm testing completed satisfactory.