Permit Information
Permit NumberFIR13-00264
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 815 W ANN MORRISON PARK DR
Project NameCheerleader Restaurant
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of providing a new wet pipe system throughout the building. The 6” underground is existing. The system consists of two trees. The mains are 4” and the branch piping is 1½”. There is a small 2½”dry system protecting the canopies. The building is divided into two spaces. The largest area is a restaurant. The smaller area is unoccupied at this time. The entire system was design for Ordinary Hazard II to support future occupancies.

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/4/201311/4/201311/5/2013PPASS
DetailsForrest France
Corrections finished. Final walkthrough passed. Fire sprinkler permit finaled.
INSP-Final Inspection10/31/201311/1/201311/1/2013APART
DetailsForrest France
Final pending relocation of the outside bell per plan and power supply to the air compressor.
INSP-Sprinkler Rough-in10/25/201310/25/201310/25/2013PPART
DetailsForrest France
24 hr. air test of the new dry system completed with no pressure loss at the guage.
INSP-Sprinkler Rough-in/Hydro10/24/201310/24/201310/24/2013APART
DetailsTroy Cobbley
Dry system air test started at 9:30 with 44psi on the guage.
INSP-Sprinkler Rough-in10/22/201310/22/201310/22/2013APART
DetailsForrest France
Okay to cover overhead work at the kitchen grid ceilings.
INSP-Sprinkler Rough-in/Hydro10/21/201310/21/201310/21/2013PPART
DetailsForrest France
Overhead hydrostatic test completed and passed for both the dry and wet systems.
INSP-Sprinkler Rough-in8/19/20138/19/20138/19/2013APART
DetailsForrest France
OH rough-in inspection completed.
INSP-Sprinkler Rough-in8/12/20138/13/20138/13/2013APART
DetailsForrest France
Completed overhead rough-in of the new wet and dry systems. Noted one missing EQ brace at the lower level 4" main, provide seismic clearance at the main through masonry wall west end. Additional uprights and branchline to be shown on record drawings. Non-sprinklered combustible concealed pockets to be filled with insulation as discussed with contractor to meet the allowable exceptions per NFPA. Discussed hydro and air testing, riser room yet to be built, FDC location, etc.
INSP-Supply line flush7/1/20137/1/20137/1/2013PPASS
DetailsForrest France
UG fire supply line flush completed satisfactory.