INSP-Final Inspection | 7/16/2013 | 7/16/2013 | 7/16/2013 | P | PASS |
Forrest France
|
|
|
Noted correction items completed. Hood suppression system operated correctly under test conditions. Permit finaled.
|
INSP-Final Inspection | 7/12/2013 | 7/15/2013 | 7/15/2013 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Alex Phone #: ###-####
|
INSP-Final Inspection | 7/10/2013 | 7/11/2013 | 7/11/2013 | P | FAIL |
Forrest France
|
|
|
Manual pull needs relocated per IFC 904.11.1, electrical wiring to be in accordance with NFPA 70 (IFC 904.3.1), equipment layout to match system design and nozzle location. No testing completed due to corrections needed.
|
INSP-Final Inspection | 7/10/2013 | 7/10/2013 | 7/10/2013 | P | DEFR |
Forrest France
|
|
|
Alex Phone #: ###-#### *Rescheduled per Alex
|