Permit Information
Permit NumberFIR13-00308
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 601 W GOWEN RD
Project NameWPS Office Addition
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a new two-story office addition. The first floor is connected to the existing grid as a center fed 2 ½” loop with 1 ¼” branch lines. The second floor is connected to the secondary main of the existing grid. A 3” feed main supplies a 2 ½” center feed system with 1 ¼” branch lines.

Plan Mod #1 – 10/15/2013
Revised drawing due to owner changes. Added ceilings and clouds. (There are no additional changes in this review)

Plan Mod #2 - 9/08/2014
Revision due to owner changes. New Reception #101, Hallway and room to the left of Photo B #106. (There are no additional changes in this review)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/16/20149/16/20149/16/2014APASS
DetailsForrest France
Plan modification site verified. Final inspection passed. Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in9/15/20149/16/20149/16/2014APART
DetailsForrest France
Rough-in inspections for changes at the 1st and 2nd floor office and common areas east side completed.
INSP-Final Inspection8/15/20148/18/20148/18/2014APART
DetailsForrest France
Final pending revised drawings to include work at the 1st and 2nd floor reception and adjacent office, open and breakroom areas not originaly included.
INSP-Sprinkler Rough-in6/23/20146/24/20146/24/2014APART
DetailsForrest France
Inspection completed for overhead work at the reception area and adjacent offices- relocated heads and adjusted coverage.
INSP-Sprinkler Rough-in6/20/20146/23/20146/23/2014PPART
DetailsForrest France
INSP-Sprinkler Rough-in5/16/20145/19/20145/19/2014PPART
DetailsForrest France
Inspection for modifications at the 1st and 2nd floor existing adjacent office and breakroom areas. This work to be shown on revised drawings per discussion.
INSP-Sprinkler Rough-in4/22/20144/22/20144/22/2014APART
DetailsForrest France
Walkthrough of the 1st and 2nd floor new office addition completed. Noted obstructions to coverage at the 2nd floor executive locker room, covered sprinkler and missing escutcheon at mechanical room. Remainder okayed.
INSP-Sprinkler Rough-in/Hydro2/18/20142/19/20142/19/2014APART
DetailsForrest France
Overhead hydrostatic test of the new system piping completed satisfactory.
INSP-Sprinkler Rough-in/Hydro2/14/20142/18/20142/18/2014ADEFR
DetailsForrest France
Leroy is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in1/17/20141/21/20141/21/2014PPASS
DetailsTroy Cobbley
Todays inspection was for the pendant heads installed in the suspended "clouds". Installation and spacing appeared ok.
INSP-Sprinkler Rough-in/Hydro12/30/201312/30/201312/30/2013PPART
DetailsForrest France
Refer to dated annotations for areas okayed to cover.
INSP-Sprinkler Rough-in12/26/201312/27/201312/27/2013APART
DetailsForrest France
Okay to cover fire sprinkler work at the second floor north end stairway grid ceiling.
INSP-Sprinkler Rough-in10/3/201310/4/201310/4/2013PPART
DetailsForrest France
Inspection regarding conditions per NFPA 13 2010 8.6.5.1.2 and 8.6.5.3.3.
INSP-Sprinkler Rough-in9/20/20139/23/20139/23/2013APART
DetailsForrest France
Overhead work at the first floor mens and womens restrooms and adjacent corridor soffit, and second floor RR's and mechanical room are okay for sheetrock ceiling cover. Discussed project schedule, hydrostatic testing, and plan modifications due to field changes.
INSP-Sprinkler Rough-in9/19/20139/20/20139/20/2013PCANC
DetailsForrest France
Overbooked