Permit Information
Permit NumberFIR13-00312
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project NameMicron
Customer NumberC18332
ePlanReviewNo
Description
Fire Alarm System: C18332 - B15 Re-Purpose Fabrication Area, the Pyrotronics main control panel is obsolete. A new panel exists, which would be facilitated. New devices to be Edwards Technology.
All required pull stations, horn/strobes etc. in common areas of the building will be installed under this project.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20165/10/20165/10/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete.
INSP-Sprinkler Rough-in/Hydro3/17/20163/17/20163/17/2016APASS
DetailsJim Page
Audio/visuals tested for first level, all A/V devices inspected passed operational and visual inspection. A/V testing complete for this scope of work.
INSP-Final Inspection2/10/20162/10/20162/10/2016APART
DetailsJim Page
Devices associated with fire sprinkler systems tested, tampers, flow switches, high/low air switches and pre-action pressure switches, devices operated correctly, water flow pressure switches on pre-action systems reported to fire panel as a supervisory, pre-action flow switches will be reprogrammed to come in as water flow alarm with exterior bell activation. Riser rooms inspected/tested were located on the east side of building and southeast side of building.
INSP-Final Inspection11/3/201511/3/201511/3/2015APART
DetailsJim Page
Inspected visual/audible notification for mezz/mech level, items inspected passed/complete
INSP-Final Inspection3/31/20154/1/20154/1/2015APART
DetailsForrest France
Completed walkthrough and functional testing for fire alarm work at the basement level plan sheets 2.0.1 thru 2.0.5. Items noted include; adjust visual notification coverage at three locations to meet spacing at end of corridors, delete or relocate SD for door hold release at NW side, noted non-functional horns at various areas, device address changes at the solvents rooms completed while on site. Also noted missing HD at the elevator machine room-(state elevator certification dated 2014). Manual pull stations, smoke detectors and visual notification tested satisfactory.