Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberFIR13-00409
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 1109 W MAIN ST
Project NameOWYHEE PLACE
Customer Number 
ePlanReviewYes
Description
Replacement of existing fire alarm system during building renovation.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/19/20148/26/20148/26/2014APASS
DetailsForrest France
Verified previous correction items and plan modification. Remainder of fire alarm work completed and passed inspection. Permit finaled.
INSP-Alarm Testing7/11/20147/11/20147/11/2014APART
DetailsForrest France
Fire alarm work tested today includes sprinkler monitoring-pump, riser, floor control manifolds-, elevator recall functions at car #1, machine rooms for elevators 1, 2 and 3, occupant notification throughout core areas basement to 7th floor, nac and FACP batteries, SD's at the freight elevator, MP, SD at nac's, ID's at the 2nd floor, DD for RTU 3, lobby door mags, offiste monitoring. Need to provide plan modification for added ID's and to include field changes in system layout such as relocated FACP, HD at hoistways, added lobby SD, PIV, relay for lobby mag locks, etc. Post points map. Some items corrected while on site including descriptor at west 1st floor waterflow, added HD at machine room 2/3, nac B battery trouble, deck secured SD, tamper 1st floor east. Need to remove HD at elevator hoistway #1, repair door hold at the basement level.
INSP-Final Inspection7/10/20147/10/20147/10/2014PPART
DetailsForrest France
Completed initial walkthrough at core areas. Identified adjustments to be made at some locations.
INSP-Final Inspection7/3/20147/7/20147/7/2014APART
DetailsForrest France
Notification at the kitchen and bakery areas 1st floor tested satisfactory.
INSP-Final Inspection6/30/20146/30/20147/1/2014PPART
DetailsForrest France
Completed funcitional testing and inspection of fire alarm work at the 2nd, 3rd and 4th floor apartments and common corridors including notification and in-duct detectors. Also tested floor control manifolds for the 2nd, 3rd and 4th floor fire protection - tampers okayed, need to replace 3rd and 4th floor flow switches.
INSP-Sprinkler Rough-in6/12/20146/13/20146/13/2014APART
DetailsForrest France
Randy Phone #: ###-####