INSP-Final Inspection | 8/19/2014 | 8/26/2014 | 8/26/2014 | A | PASS |
Forrest France
|
|
|
Verified previous correction items and plan modification. Remainder of fire alarm work completed and passed inspection. Permit finaled.
|
INSP-Alarm Testing | 7/11/2014 | 7/11/2014 | 7/11/2014 | A | PART |
Forrest France
|
|
|
Fire alarm work tested today includes sprinkler monitoring-pump, riser, floor control manifolds-, elevator recall functions at car #1, machine rooms for elevators 1, 2 and 3, occupant notification throughout core areas basement to 7th floor, nac and FACP batteries, SD's at the freight elevator, MP, SD at nac's, ID's at the 2nd floor, DD for RTU 3, lobby door mags, offiste monitoring. Need to provide plan modification for added ID's and to include field changes in system layout such as relocated FACP, HD at hoistways, added lobby SD, PIV, relay for lobby mag locks, etc. Post points map. Some items corrected while on site including descriptor at west 1st floor waterflow, added HD at machine room 2/3, nac B battery trouble, deck secured SD, tamper 1st floor east. Need to remove HD at elevator hoistway #1, repair door hold at the basement level.
|
INSP-Final Inspection | 7/10/2014 | 7/10/2014 | 7/10/2014 | P | PART |
Forrest France
|
|
|
Completed initial walkthrough at core areas. Identified adjustments to be made at some locations.
|
INSP-Final Inspection | 7/3/2014 | 7/7/2014 | 7/7/2014 | A | PART |
Forrest France
|
|
|
Notification at the kitchen and bakery areas 1st floor tested satisfactory.
|
INSP-Final Inspection | 6/30/2014 | 6/30/2014 | 7/1/2014 | P | PART |
Forrest France
|
|
|
Completed funcitional testing and inspection of fire alarm work at the 2nd, 3rd and 4th floor apartments and common corridors including notification and in-duct detectors. Also tested floor control manifolds for the 2nd, 3rd and 4th floor fire protection - tampers okayed, need to replace 3rd and 4th floor flow switches.
|
INSP-Sprinkler Rough-in | 6/12/2014 | 6/13/2014 | 6/13/2014 | A | PART |
Forrest France
|
|
|
Randy Phone #: ###-####
|