Permit NumberFIR13-00579
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1109 W MAIN ST
Project NameOwyhee Place
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of connecting to existing mains and sprinklering a 3 floor residential wing. The piping is al CPVC with 2” mains and 1” lines.
(OWYHEE PLACE - APARTMENTS, MEETING ROOM CORE, AND OFFICE CORE) (10-25-13 PLAN MODIFICATION TO DELETE A PREVIOUSLY PROPOSED ROOF POP-UP AT THE 7TH STORY, INSTALL ADDITIONAL WINDOWS IN THE SOUTH EXTERIOR WALL OF THE 7TH STORY, RAISE THE CEILING OF THE 7TH STORY TO CREATE MORE ROOM VOLUME, TO REPLACE EXISTING HISTORIC EXTERIOR WINDOWS IN THE SOUTH AND WEST EXTERIOR WALLS OF THIS BUILDING WITH NEW WINDOWS, AND TO MODIFY THE DESIGN OF THE WALKWAY ACROSS THE ROOF GIVING ACCESS TO THE 2ND EXIT FROM THE 7TH STORY.) Fire sprinkler system used for area, story, and height increase. To renovate an existing 7 story building. Interior non-structural demolition work was done under permit BLD13-01010. On August 23, a plan modification was done to the demolition permit to include the removal of exterior nonstructural veneer brick on the Main Street and 11th Street sides of the historic portion of this building at the 1st story and to include the removal of the fire escape from the South exterior wall of the historic portion of this building. Early start permit BLD13-01955 was also issued. A portion of this building is historic and other portions are NOT historic. The 2nd, 3rd, and 4th stories of the non-historic former West hotel wing will be converted to 36 rental apartments (total occupant load of 130). This permit is intended to establish a Certificate of Occupancy for the new apartments. Alterations to the West apartment wing are regulated by the energy code. This permit does not establish a Certificate of Occupancy for any other portion of the building. Core work will also be done under this permit within the 7 story historic portion of this building. Alterations to the historic portion of this building are not regulated by the energy code. Certificate of Occupancies will be established for tenants located within the historic portion of this building, including the 7th story terrace, under future separate tenant improvement permits. Within the historic portion, new restrooms will be provided on the 1st story and on the 2nd story. Assembly rooms on the 2nd story will be expanded or combined. Egress will be upgraded on all stories. Trellis structures at grade will be constructed. New storefront windows will be installed at grade. Several other windows will also be replaced. Core areas on the 3rd, 4th, 5th, and 6th stories will be remodeled with new restrooms created. A new mechanical shaft will be constructed. The vault below the Main Street sidewalk will be abandoned. The sidewalk will be demolished, a retaining wall will be constructed below and parallel with the North exterior building wall, and the vault will be backfilled with structural fill. Special Inspection is required for concrete, masonry, welding, and epoxy anchors. This building will be connected to the downtown geothermal system. The fire sprinkler system shall comply with NFPA 13 and the fire alarm system shall comply with NFPA 72 as new systems and as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20149/23/20149/23/2014APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection7/23/20147/23/20147/23/2014APART
DetailsForrest France
Previous correction items verified for completion.
INSP-Final Inspection6/30/20146/30/20147/1/2014PPART
DetailsForrest France
Noted items on walkthrough of the 2nd, 3rd and 4th floor apartment units include taped head/missing escutcheon at unit 206, need to provide intermediate temp head at unit 312 adjacent to HVAC diffuser, flow switches at the 3rd and 4th floor are malfunctional, missing outside waterflow bell.
INSP-Sprinkler Rough-in3/20/20143/20/20143/20/2014PPART
DetailsForrest France
Okay to cover overhead work at the 3rd floor mens and womens restrooms.
INSP-Sprinkler Rough-in2/26/20142/27/20142/27/2014APART
DetailsForrest France
As noted on plans
INSP-Sprinkler Rough-in2/25/20142/26/20142/26/2014APART
DetailsTroy Cobbley
One small soffit is ok to cover, see marked plans, the other areas request for inspection need sheet rock removed so I can see the piping.
INSP-Sprinkler Rough-in2/6/20142/7/20142/7/2014APART
DetailsForrest France
Okay to cover fire sprinkler work at the second floor units- kitchens and bathrooms.
INSP-Sprinkler Rough-in/Hydro2/4/20142/5/20142/5/2014APART
DetailsForrest France
Completed overhead hydrostatic test of the wet system 2nd floor west wing. Also completed cover inspection of the corridor drop ceiling, unit kitchens and bathroom ceilings. Noted exposed combustible construction above the ceiling lids to be covered with sheetrock.
INSP-Sprinkler Rough-in/Hydro1/13/20141/14/20141/14/2014APART
DetailsForrest France
Completed hydrostatic testing for the 3rd floor west wing units and corridor.
INSP-Sprinkler Rough-in/Hydro12/11/201312/11/201312/11/2013PPASS
DetailsForrest France
Hydro 4th floor residential area passed.
INSP-Sprinkler Rough-in12/4/201312/4/201312/4/2013PPART
DetailsForrest France
Overhead work at the 4th floor corridor including the remainder of hard lid soffits are okay for cover. One pendent head to be adjusted as discussed.
INSP-Sprinkler Rough-in11/20/201311/20/201311/20/2013PPART
DetailsForrest France
Verified soffits at the 4th floor guest rooms adjacent to outside windows are filled with non-combustible insulation.
INSP-Sprinkler Rough-in11/7/201311/8/201311/8/2013APART
DetailsForrest France
Rough-in inspection completed for work at the 2nd floor guest rooms- okayed for ceiling cover.
INSP-Sprinkler Rough-in10/31/201310/31/201311/1/2013PPART
DetailsForrest France
Rough-in inspection for the 3rd floor unit rooms only- Identified concealed combustible spaces at some areas in need of coverage or meet allowable conditions per NFPA 13. Clarify if space between ceiling and deck above the kitchens will be sheetrocked. Plan modification to include deleted pendents at the end of lines in some units. Branchlines and head spacing okayed.
INSP-Sprinkler Rough-in10/30/201310/30/201310/30/2013PPART
DetailsCraig D. Hanson
this was for 4th floor cover of branchlines into rooms. Main and connection will be installed below hard lid and will be inspected later. No hydro of pipe being covered, installer responsible for any leaks in covered pipe.concealed sofit on each side of 4th floor needs insulation or to be spinkled.